Select transformer data:


Transformer Output Power (Sn) (3) :
kVA
Transformer Voltage:



(1) The design presented are valid for WEG transformers, class of insulation of 15 kV. Other situations, on request.

(2) The short-circuit level supplied is calculated on the transformer secondary terminals, considering only its impedance.

(3) The tables are limited to 1500kVA once on larger output rating transformers, design are done, on most cases, as per customer specification. On this case, installation short-circuit level may change significantly.

(4) The distribution circuit breakers may be selected for the rated current values given on the sample table limited to the short-circuit interruption capacity version selected for each transformer.

(5) On substations with two or more transformers connected in parallel at the lower voltage, for short-circuit level determination, you should consider the sum of outputs in kVA and the average of the percentage impedance values Z (%).

(6) An overload factor of 15% was taken into account in order to dimension the transformer low voltage circuit breaker.


Voltage DWB160 DWB250 DWA400 DWA800 DWA1600
Breaking capacity level Vca (60Hz) B N (3) L (3) B N (3) L (3) N H (3) N H (3) S H (3)
Maximum short circuit breaking capacity (kA) Icu (O-t-CO) (4) 220/240V 25 50 120 42 85 120 65 80 65 80 80 100
380/415V 16 30 80 16 35 80 35 65 35 65 50 65
440V 10 20 80 15 30 80 35 65 35 65 50 65
460/500V 5 8 65 5 8 65 25 50 25 50 40 50
Protection type
Current range
Distribution Fixed thermal / Fixed magnetic 16 20 25 32 40 50 63 70 80 90 100 110 125 150 160
Adjustable thermal / Fixed magnetic 64/80   80/100   100/125   126/160 80/100   100/125   125/160
160/200   200/250
Adjustable thermal / Adjustable magnetic 80/100   100/125   125/160   160/200
200/250   250/320   320/400
225/320   280/400   350/500
440/630   560/800
630/800   800/1000
1000/1250   1260/1600


Power factor correction